4C+E Circular PVC SWA

Applications

For mains, submains and sub-circuits unenclosed, in conduit, buried direct or in underground ducts for buildings and industrial plants where mechanical damage may occur. Where out of balance currents may require a neutral equal in size to the active.

SKU: N/A Category:

Product Description

4Core+E, copper conductors, 0.6/1kV, V-90 insulated, PVC bedded, GSW Armoured and 5V-90 Sheathed to AS/NZS 5000.1

Cable Design

CONDUCTOR
  • Plain annealed copper conductor, Class 2, Class 1 (AS/NZS 1125)
  • Maximum continuous operating temperature: 75°C (AS/NZS 3008.1)
    (Can also be operated at temperatures up to 90°C)
INSULATION
  • PVC (V-90)
  • Colour: Red, Blue,White, Green/Yellow, Blue
SHEATH
  • PVC (5V-90)
  • Colour: Orange
STANDARDS
  • AS/NZS 1125
  • AS/NZS 5000.1
  • AS/NZS 3808

Cable Characteristics:

MAXIMUM OPERATING TEMPERATURE +75℃ MINIMUM OPERATING TEMPERATURE -15℃
MINIMUM BENDING RADIUS 12D BEHAVIOUR IN FLAME AND FIRE No Fire Performace
MECHANICALIMPACTRESISTANCE Moderate Impact FLEXIBILITY Semi Rigid

Technical Specifications:

SKUCross SectionEarth conductor cross sectionNo & Diameter of Wires No/mmNo & Diameter of Wires EarthNominal insulation thicknessinsulation thickness earthArmour wire diameter mmDiameter under armour mmNominal Sheath thickness mmOverall Diameter mmApprox. mass kg/kmMinimum Bending radius mm
ELDB2DVST1H
ELDB2DVST2H
ELDB2DVST04
ELDB2DVST06
ELDB2DVST10
ELDB2DVST16
ELDB2DVST25
ELDB2DVST35
ELDB2DVST50
ELDB2DVST70
ELDB2DVST95
ELDB2DVST120
ELDB2DVST150
ELDB2DVST185
ELDB2DVST240
ELDB2DVST300

 

Electrical Specifications:

Reactance (Xc)
at 50 Hz
Ω/km
Maximum D.C.
Resistance at
20°C
Ω/km
Current Rating Nominal Cross Section
Area mm2
Underground
wiring
Enclosure
A
Buried
Direct
A
Enclosed Unenclosed
Wiring enclosure
in air
A
Exposed to
Sun
A
Touching
A
Spaced
A
0.111 13.6 18 18 14 12 15 16 1.5
0.102 7.41 25 25 20 17 22 23 2.5
0.102 4.61 33 33 25 23 29 31 4
0.0967 3.08 42 42 33 29 37 40 6
0.0966 1.83 55 55 44 39 51 54 10
0.0861 1.15 73 96 58 51 68 72 16
0.0853 0.727 94 125 76 67 91 97 25
0.0826 0.524 114 150 94 82 112 120 35
0.0797 0.387 136 178 112 99 137 146 50
0.0770 0.268 170 219 142 123 172 185 70
0.0766 0.193 208 263 177 150 213 228 95
0.0743 0.153 237 300 202 172 247 265 120
0.0745 0.124 266 336 228 194 282 303 150
0.0744 0.0991 304 379 263 220 324 348 185
0.0735 0.0754 359 438 316 256 383 412 240
0.0732 0.0601 404 493 288 438 472 300

Note:

Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-C012.

The values in this table are for typical Australia installation conditions:
  • Ambient Air Temperature 40°C
  • Soil Temperature 25°C
  • Soil Thermal Resistivity 1.2 °C.m/W
  • Depth of Burial 0.5 m

For using current rating in other installation conditions (methods of installation, Ambient Air Temperature, Soil Temperature, Soil Thermal Resistivity and Depth of Burial) or using other electrical characteristics, Refer to AS/NZS 3008.1.1 or electrical data, at the end of this catalogue.

Current Rating

Table 1

Current Ratings (Two single core –  PVC – 75C)

 

Cable type: Two Single Core (Applies to non-armoured, sheathed or unsheathed)

Insulation type: Thermoplastic (V-75, V-90, V-90HT, HFI-75-TP or HFI-90-TP)

Maximum conductor Temperature: 75C

Reference Ambient Temperature: 40C in air, 25C in Ground

Conductor size

mm2

Current carrying capacity, A
Unenclosed
Spaced Spaced

from

Surface

Touching Exposed

to Sun

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 16 17 16 17 13 13 8 8
1.5 21 21 21 21 16 17 10 10
2.5 30 29 29 28 23 22 13 13
4 40 38 39 38 31 30 18 17
6 51 49 49 48 40 38 22 21
10 69 69 67 67 54 54 30 29
16 92 91 72 89 88 69 72 71 56 39 38 30
25 124 121 96 119 115 92 97 94 75 50 49 39
35 153 150 119 145 143 113 119 117 92 61 59 47
50 187 189 145 177 179 137 146 147 113 72 73 56
70 238 238 184 223 224 173 184 185 143 89 89 69
95 295 287 229 276 269 214 230 223 178 107 104 83
120 344 341 267 321 317 249 267 265 208 122 120 95
150 395 393 307 367 365 285 308 306 239 137 135 106
185 459 450 357 424 416 331 358 351 279 154 150 120
240 549 541 427 505 498 394 428 422 334 177 173 138
300 636 624 495 582 571 456 495 486 388 198 192 155
400 744 752 583 676 682 535 577 583 456 221 218 175
500 867 876 685 780 787 624 668 675 535 245 240 196
630 1014 1036 808 897 914 730 770 785 627 269 266 219

 

Table 1 (continued)

Conductor size

mm2

Current carrying capacity, A
Enclosed Thermal insulation Buried direct Underground wiring enclosure
Wiring

Enclosure

in Air

Partially surrounded by

thermal

insulation

Completely

surrounded by

thermal

insulation

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 13 14 11 6 18 18 19 21
1.5 18 18 14 8 23 23 23 26
2.5 24 24 20 12 32 32 31 36
4 32 31 25 16 41 41 40 47
6 41 40 33 20 52 52 50 58
10 54 54 44 27 69 69 68 77
16 70 69 54 56 43 36 28 122 95 89 87 69 99 77
25 94 91 73 75 58 48 37 158 123 116 112 90 129 100
35 112 110 87 90 70 59 46 190 147 139 136 108 155 120
50 138 139 107 110 86 225 174 168 168 130 186 145
70 170 169 132 136 105 277 215 206 205 160 228 177
95 212 206 164 169 131 332 257 252 244 195 278 215
120 242 237 188 193 150 378 294 287 282 223 316 245
150 282 278 219 225 175 424 329 329 324 255 354 274
185 320 312 249 256 199 480 373 373 363 291 408 317
240 381 373 298 305 238 556 434 438 429 342 472 368
300 628 491 496 493 388 546 425
400 713 564 575 572 454 621 487
500 805 644 649 663 520 721 570
630 904 737 750 754 611 816 652

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 2

Current Ratings (Two single core –  XLPE – 90C)

 

Cable type: Two Single Core (Applies to non-armoured, sheathed or unsheathed)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 or R-CSP-90

Maximum conductor Temperature: 90C

Reference Ambient Temperature: 40C in air, 25C in Ground

 

Conductor size

mm2

Current carrying capacity, A
Unenclosed
Spaced Spaced

from

Surface

Touching Exposed

to Sun

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 20 21 20 21 16 16 12 13
1.5 26 26 25 26 20 20 15 16
2.5 36 35 36 34 28 27 21 21
4 48 46 47 46 37 36 28 27
6 61 59 60 58 47 46 36 34
10 84 83 82 81 65 64 48 48
16 112 110 87 108 106 84 86 85 67 64 63 50
25 151 147 117 145 141 112 117 114 91 86 83 66
35 186 183 144 177 174 137 144 141 111 105 103 81
50 228 231 177 216 218 167 176 178 136 127 128 99
70 291 292 226 273 274 212 224 225 174 160 161 124
95 361 351 280 338 328 262 278 271 216 197 192 153
120 422 418 328 393 389 305 325 322 253 229 226 178
150 486 483 377 451 448 350 375 373 291 262 260 204
185 565 555 439 522 512 406 436 428 340 303 296 236
240 678 668 527 622 613 485 522 515 408 359 353 280
300 787 772 612 718 705 562 605 594 473 413 404 323
400 923 933 723 836 843 660 708 715 559 478 480 377
500 1078 1090 850 966 975 772 821 830 656 550 552 439
630 1261 1288 1003 1113 1135 904 950 969 772 629 639 511

 

Table 2 (continued)

Conductor size

mm2

Current carrying capacity, A
Enclosed Thermal insulation Buried direct Underground wiring enclosure
Wiring

Enclosure

in Air

Partially surrounded by

thermal

insulation

Completely

surrounded by

thermal

insulation

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 16 17 13 8 20 20 21 24
1.5 21 21 16 10 26 26 26 30
2.5 30 28 24 14 36 36 35 41
4 38 37 30 19 46 46 45 53
6 47 46 38 24 58 58 56 66
10 65 64 52 32 78 78 77 87
16 84 82 65 67 52 43 33 139 107 100 98 78 112 87
25 113 109 87 90 70 58 45 179 139 131 127 102 146 114
35 135 132 105 108 84 72 56 215 167 157 154 122 175 136
50 166 167 129 133 103 255 198 189 190 147 211 164
70 204 204 159 164 127 313 243 233 232 181 258 200
95 255 248 198 204 158 375 291 285 276 221 309 239
120 292 286 226 233 181 427 332 325 319 252 358 278
150 329 336 255 263 204 480 372 365 368 283 401 311
185 387 377 301 309 241 543 423 423 412 329 463 359
240 461 452 360 369 288 630 492 497 486 388 536 417
300 711 556 562 548 440 620 482
400 808 638 653 650 516 706 553
500 913 729 739 733 590 800 632
630 1026 833 856 860 695 930 740

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table3 Continued

Conductor size

mm2

Current carrying capacity, A
Enclosed Thermal insulation Buried direct Underground wiring enclosure
Wiring

Enclosure

in Air

Partially surrounded by

thermal

insulation

Completely

surrounded by

thermal

insulation

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 12 13 10 6 16 16 16 19
1.5 15 15 12 8 20 20 20 24
2.5 21 20 17 12 27 27 26 33
4 28 27 23 16 36 36 35 43
6 35 34 28 20 45 45 43 53
10 47 46 37 27 59 59 58 70
16 62 61 48 50 39 36 28 104 81 78 76 60 90 70
25 81 78 63 64 50 48 38 134 104 100 97 78 117 91
35 100 98 78 80 62 59 46 160 124 122 119 94 140 108
50 119 120 92 95 74 190 147 144 145 112 168 131
70 152 152 118 122 94 233 181 180 180 140 205 159
95 183 178 142 147 114 279 216 217 210 168 250 194
120 217 213 169 173 135 317 247 252 247 196 283 220
150 244 241 190 195 152 356 276 283 279 220 317 246
185 284 277 222 227 177 402 313 325 316 253 365 284
240 331 336 269 265 207 465 364 377 376 295 422 329
300 388 379 305 311 244 524 412 434 423 341 488 380
400 442 461 351 353 281 593 471 492 504 391 553 434
500 523 520 421 418 337 668 537 571 566 459 641 507
630 588 592 481 471 385 748 612 639 641 523 723 578

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 4

Current Ratings (Three single core – XLPE – 90C)

 

Cable type: Three Single Core (Applies to non-armoured, sheathed or unsheathed)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 or R-CSP-90

Maximum conductor Temperature: 90C

Reference Ambient Temperature: 40C in air, 25C in Ground

Conductor size

mm2

Current carrying capacity, A
Unenclosed
Spaced Spaced

from

Surface

Touching Exposed

to Sun

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 19 20 16 17 16 16 12 13
1.5 25 25 21 22 20 20 15 16
2.5 35 33 30 29 28 27 21 21
4 46 45 40 38 37 36 28 27
6 59 57 50 49 47 46 36 34
10 81 80 69 69 65 64 48 48
16 108 106 84 92 91 71 86 85 67 64 63 50
25 146 142 113 125 121 97 117 114 91 86 83 66
35 180 177 140 154 151 119 144 141 111 105 103 81
50 221 223 171 188 191 146 176 178 136 127 128 99
70 282 283 219 240 241 186 224 225 174 160 161 124
95 350 341 271 298 290 232 278 271 216 197 192 153
120 410 406 318 349 346 271 325 322 253 229 226 178
150 472 470 366 403 400 313 375 372 291 262 260 203
185 560 540 427 468 459 365 435 427 339 302 296 235
240 660 651 513 560 553 438 521 514 407 358 352 280
300 766 752 596 648 637 508 602 591 472 410 402 322
400 899 909 705 756 764 599 702 709 557 474 477 376
500 1051 1062 829 874 884 703 812 821 652 544 546 437
630 1230 1256 978 1010 1030 824 938 956 765 621 630 507

 

Table 4 Continued

Conductor size

mm2

Current carrying capacity, A
Enclosed Thermal insulation Buried direct Underground wiring enclosure
Wiring

Enclosure

in Air

Partially surrounded by

thermal

insulation

Completely

surrounded by

thermal

insulation

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 15 15 12 8 18 18 19 22
1.5 18 19 15 10 22 22 23 27
2.5 25 24 20 14 31 31 30 38
4 33 31 26 19 40 40 38 49
6 42 41 34 24 50 50 49 60
10 56 55 45 32 67 67 66 79
16 72 73 56 58 45 43 33 117 91 86 85 66 101 79
25 97 94 75 77 60 58 45 151 117 113 109 87 132 103
35 120 118 93 96 75 72 56 180 140 137 134 106 158 122
50 143 144 111 114 89 214 166 163 163 126 190 147
70 183 183 142 146 114 262 203 203 203 158 232 180
95 220 214 171 176 137 313 243 244 237 190 276 214
120 261 256 203 209 162 356 277 284 279 221 320 248
150 295 291 229 236 183 400 310 320 316 249 358 277
185 335 334 261 268 209 452 352 363 357 283 413 321
240 399 391 312 320 250 523 409 426 416 333 477 371
300 469 458 368 375 294 589 463 491 479 385 552 430
400 543 533 424 427 339 668 530 557 554 442 626 491
500 633 630 509 506 407 752 604 648 642 520 707 559
630 714 719 583 571 466 843 688 727 729 593 820 654

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 5

Current Ratings (Two core – PVC – 75C)

 

Cable type: Two Core Sheathed (Applies to cables with or without earth core, armoured or unarmoured, including neutral screened cables)

Insulation type: Thermoplastic (V-75, V-90, V-90HT, HFI-75-TP or HFI-90-TP)

Maximum conductor Temperature: 75C

Reference Ambient Temperature: 40C in air, 25C in Ground

Conductor size

mm2

Current carrying capacity, A
Unenclosed Enclosed
Spaced Touching Exposed

to Sun

Wiring

Enclosure

in Air

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 15 16 14 15 11 12 13 13
1.5 19 20 18 18 14 14 16 17
2.5 27 26 26 25 20 19 23 23
4 37 35 34 33 27 26 30 29
6 46 45 44 42 34 32 39 38
10 64 63 60 59 46 45 52 51
16 85 83 66 80 78 62 60 59 47 68 68 52
25 113 110 88 107 104 83 79 77 62 90 87 70
35 139 137 108 131 128 101 97 94 75 112 109 87
50 170 171 132 159 161 124 116 117 90 133 134 103
70 215 215 167 201 202 156 145 145 112 170 169 132
95 265 257 205 248 241 192 175 170 136 204 198 158
120 307 304 239 288 285 224 202 199 157 241 236 187
150 351 348 272 328 326 255 227 225 177 271 267 210
185 403 395 314 377 370 294 258 252 201 313 305 244
240 477 470 373 446 439 349 300 294 235 364 368 285
300 547 537 429 511 502 401 339 331 266 424 415 333
400 631 636 500 589 593 467 384 384 305 482 500 383
500 716 728 575 668 678 536 429 431 345 561 564 451

 

 

Table 5 Continued

Conductor size

mm2

Current carrying capacity, A
Thermal insulation Buried direct Underground wiring enclosure
Partially surrounded by

thermal

insulation, unenclosed

Partially

surrounded by

thermal

insulation, in a wiring

enclosure

Surrounded by

thermal

insulation, unenclosed

Completely

surrounded by

thermal

insulation, in a wiring

enclosure

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible
1 11 10 7 6 17 17 18
1.5 14 13 9 8 21 21 22
2.5 20 19 13 12 30 30 29
4 27 24 17 15 39 39 38
6 35 31 22 20 50 50 48
10 48 42 30 26 66 66 65
16 64 49 54 42 40 31 34 26 114 88 86 85 66
25 85 66 72 56 53 41 45 35 147 114 112 108 87
35 105 81 90 70 65 51 56 43 178 138 136 133 106
50 127 99 107 83 211 163 162 163 126
70 161 125 136 105 259 201 202 202 157
95 198 154 163 127 311 241 243 236 189
120 230 179 192 150 355 276 282 277 220
150 263 204 217 168 398 309 317 313 246
185 302 235 250 195 449 350 363 353 283
240 357 279 291 228 520 406 421 419 329
300 409 321 340 266 586 460 483 472 379
400 471 373 386 306 663 526 548 560 434
500 534 429 449 360 741 595 628 629 504

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 6

Current Ratings (Two core – XLPE – 90C)

 

Cable type: Two Core Sheathed (Applies to cables with or without earth core, armoured or unarmoured, including neutral screened cables)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 or R-CSP-90

Maximum conductor Temperature: 90C

Reference Ambient Temperature: 40C in air, 25C in Ground

Conductor size

mm2

Current carrying capacity, A
Unenclosed Enclosed
Spaced Touching Exposed

to Sun

Wiring

Enclosure

in Air

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 18 19 17 18 15 16 16 16
1.5 24 24 22 23 19 20 20 20
2.5 34 32 31 30 27 26 28 27
4 45 34 42 40 36 35 37 35
6 57 55 53 51 46 44 46 44
10 78 78 73 72 63 62 63 62
16 104 103 81 97 96 75 83 82 64 82 80 63
25 140 136 109 131 128 102 111 108 86 110 106 85
35 173 169 134 162 158 125 136 134 106 132 129 102
50 211 213 163 197 199 153 165 167 128 162 163 126
70 268 269 208 250 251 194 208 209 162 200 207 155
95 331 322 257 309 300 239 255 248 198 250 242 194
120 385 381 299 359 355 279 295 292 230 285 289 222
150 441 438 342 411 408 319 336 333 261 332 328 257
185 509 499 396 473 464 396 385 377 300 377 375 293
240 604 596 472 562 554 439 454 446 354 448 439 350
300 694 682 544 645 633 505 518 507 406 523 511 410
400 804 811 636 745 751 590 594 597 470 596 595 472
500 915 932 734 848 862 680 671 679 538 695 699 557

 

 

Table 6 Continued

Conductor size

mm2

Current carrying capacity, A
Thermal insulation Buried direct Underground wiring enclosure
Partially surrounded by

thermal

insulation, unenclosed

Partially

surrounded by

thermal

insulation, in a wiring

enclosure

Surrounded by

thermal

insulation, unenclosed

Completely

surrounded by

thermal

insulation, in a wiring

enclosure

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible
1 14 12 9 8 19 19 20
1.5 18 16 11 10 24 24 25
2.5 25 23 16 14 34 34 33
4 33 29 21 18 45 45 43
6 42 37 27 23 56 56 54
10 58 51 36 32 75 75 74
16 78 60 66 51 49 38 41 32 132 102 98 95 75
25 105 81 88 68 66 51 55 43 170 132 128 124 99
35 129 100 106 82 81 63 66 51 205 159 154 150 119
50 158 122 130 101 244 189 185 186 144
70 200 155 160 124 300 233 228 231 177
95 247 192 200 155 360 279 279 271 216
120 287 223 228 177 410 319 318 318 247
150 328 255 265 206 460 357 365 360 283
185 379 295 301 235 520 405 413 407 322
240 449 351 358 280 603 471 485 475 379
300 516 404 418 328 680 533 558 544 437
400 596 472 477 378 771 610 633 631 501
500 678 544 556 446 862 691 728 729 583

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 7

Current Ratings (Three core and Four core – PVC – 75C)

`

Cable type: Three Core and Four Core Sheathed (Applies to cables with or without earth core, armoured or unarmoured, including neutral screened cables)

Insulation type: Thermoplastic (V-75, V-90, V-90HT, HFI-75-TP or HFI-90-TP)

Maximum conductor Temperature: 75C

Reference Ambient Temperature: 40C in air, 25C in Ground

Conductor size

mm2

Current carrying capacity, A
Unenclosed Enclosed
Spaced Touching Exposed

to Sun

Wiring

Enclosure

in Air

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 13 13 12 13 9 10 11 11
1.5 16 17 15 16 12 12 14 14
2.5 23 22 22 21 17 16 20 19
4 31 30 29 28 23 22 25 24
6 40 38 37 36 29 28 33 32
10 54 54 51 51 39 38 44 43
16 72 71 56 68 67 53 51 50 40 58 57 45
25 97 94 75 91 89 71 67 65 52 76 73 59
35 120 117 93 112 110 87 82 80 64 94 92 73
50 146 148 113 137 138 106 99 100 77 112 112 87
70 185 185 143 172 173 134 123 123 96 142 142 111
95 228 222 177 213 207 165 150 145 116 177 172 137
120 265 262 206 247 244 192 172 169 134 202 199 157
150 303 301 235 282 280 219 194 192 151 228 229 177
185 348 342 272 324 318 253 220 215 172 263 257 206
240 412 407 323 383 378 301 256 251 200 316 309 248
300 472 464 372 438 430 345 288 282 227
400 544 549 434 504 508 402 326 326 260
500 616 627 498 571 580 461 363 365 294

 

 

Table 7 continued

Conductor size

mm2

Current carrying capacity, A
Thermal insulation Buried direct Underground wiring enclosure
Partially surrounded by

thermal

insulation, unenclosed

Partially

surrounded by

thermal

insulation, in a wiring

enclosure

Surrounded by

thermal

insulation, unenclosed

Completely

surrounded by

thermal

insulation, in a wiring

enclosure

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible
1 9 9 6 5 14 14 15
1.5 12 11 8 7 18 18 18
2.5 17 16 11 10 25 25 24
4 23 20 15 13 33 33 32
6 30 26 19 16 42 42 40
10 41 35 25 22 55 55 54
16 54 42 47 36 34 26 29 23 96 75 73 71 56
25 73 57 60 47 46 35 38 29 125 97 94 91 73
35 90 69 75 58 56 43 47 36 150 117 114 112 89
50 109 85 89 69 178 138 136 137 105
70 138 107 114 88 219 170 170 169 132
95 170 132 142 110 263 204 208 201 161
120 198 154 162 126 300 233 237 232 184
150 226 175 182 142 336 261 266 265 207
185 259 203 211 165 379 296 304 296 237
240 307 240 253 198 438 344 359 351 281
300 493 388 404 394 318
400 557 444 468 467 374
500 620 501 522 523 422

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

Table 8

Current Ratings (Three core and Four core – XLPE – 90C)

 

Cable type: Three Core and Four Core Sheathed (Applies to cables with or without earth core, armoured or unarmoured, including neutral screened cables)

Insulation type: X-90, X-HF-90, R-EP-90, R-CPE-90, R-HF-90 or R-CSP-90

Maximum conductor Temperature: 90C

Reference Ambient Temperature: 40C in air, 25C in Ground

Conductor size

mm2

Current carrying capacity, A
Unenclosed Enclosed
Spaced Touching Exposed

to Sun

Wiring

Enclosure

in Air

Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible Solid

or

Stranded

Flexible
1 16 16 14 15 13 13 13 14
1.5 20 20 19 19 16 17 16 17
2.5 28 27 26 26 23 22 24 23
4 38 36 35 34 30 29 30 29
6 48 46 45 43 39 37 38 37
10 66 66 62 61 53 52 53 52
16 88 87 68 83 81 64 70 69 54 68 67 53
25 119 116 93 111 108 86 94 92 73 91 89 71
35 147 144 114 137 135 106 115 113 89 114 111 88
50 180 182 140 168 170 130 140 142 109 136 136 105
70 229 230 178 213 214 165 177 177 137 173 173 134
95 283 275 220 263 256 204 217 211 168 209 202 162
120 330 327 256 306 303 238 251 248 195 246 242 192
150 377 375 293 350 348 272 285 283 222 277 274 216
185 436 428 340 404 396 315 327 320 255 322 314 251
240 517 511 405 479 472 375 385 379 302 386 379 303
300 594 584 467 549 539 432 439 430 345
400 685 692 546 632 638 504 502 504 400
500 779 794 629 718 730 579 566 573 457

 

 

Table 8 (continued)

Conductor size

mm2

Current carrying capacity, A
Thermal insulation Buried direct Underground wiring enclosure
Partially surrounded by

thermal

insulation, unenclosed

Partially

surrounded by

thermal

insulation, in a wiring

enclosure

Surrounded by

thermal

insulation, unenclosed

Completely

surrounded by

thermal

insulation, in a wiring

enclosure

Cu Al Cu Al Cu Al Cu Al Cu Al Cu Al
Solid

or

Stranded

Flexible
1 12 10 7 6 16 16 17
1.5 15 13 9 8 20 20 21
2.5 21 19 13 12 29 29 28
4 28 24 18 15 37 37 36
6 36 30 22 19 46 46 45
10 49 42 31 26 63 63 62
16 66 51 55 42 41 32 34 26 110 85 81 79 63
25 89 69 73 57 56 43 46 36 143 111 107 103 83
35 110 85 91 71 69 53 57 44 172 133 130 127 101
50 134 104 108 84 204 159 155 155 120
70 170 132 138 107 251 195 193 193 150
95 210 163 167 129 302 234 233 226 181
120 245 190 197 153 344 267 270 266 210
150 280 218 222 172 385 299 304 300 236
185 323 252 257 201 435 340 348 339 272
240 383 300 309 242 504 395 411 402 322
300 567 446 463 452 365
400 640 510 524 537 417
500 714 577 601 602 485

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

Voltage Drop

Table 9

Three Phase Voltage Drop (Vc) at 50 Hz

(Insulated, Sheathed and Non Flexible Cables)

Conductor sizemm2 Three Phase Voltage Drop (Vc) at 50 Hz, mV/A.m
Single Core Multicore
Cu Conductor Al Conductor Cu Conductor Al Conductor
75°C 90°C 75°C 90°C 75°C 90°C 75°C 90°C
Flat Touching or in Wiring Enclosure Trefoil Flat Touching or in Wiring Enclosure Trefoil Flat Touching Trefoil Flat Touching Trefoil
1 44.7 44.7 46.8 46.8 44.7 46.8
1.5 28.6 28.6 30.0 30.0 28.6 30.0
2.5 15.6 15.6 16.4 16.4 15.6 16.4
4 9.71 9.71 10.2 10.2 9.71 10.2
6 6.49 6.49 6.81 6.81 6.49 6.80
10 3.86 3.86 4.05 4.05 3.86 4.05
16 2.43 2.43 2.55 2.55 4.05 4.05 4.25 4.25 2.43 2.55 4.04 4.24
25 1.55 1.54 1.62 1.62 2.55 2.55 2.67 2.67 1.54 1.61 2.54 2.67
35 1.12 1.12 1.18 1.17 1.85 1.85 1.94 1.94 1.11 1.17 1.84 1.93
50 0.840 0.834 0.878 0.872 1.37 1.37 1.44 1.43 0.829 0.868 1.36 1.43
70 0.597 0.563 0.623 0.615 0.956 0.952 1.00 0.997 0.583 0.609 0.948 0.993
95 0.449 0.439 0.467 0.457 0.702 0.696 0.733 0.727 0.431 0.450 0.961 0.723
120 0.371 0.359 0.385 0.373 0.565 0.558 0.589 0.582 0.351 0.366 0.552 0.577
150 0.319 0.305 0.330 0.316 0.472 0.463 0.491 0.482 0.296 0.307 0.457 0.476
185 0.277 0.261 0.285 0.269 0.391 0.380 0.404 0.394 0.251 0.259 0.373 0.388
240 0.240 0.221 0.245 0.227 0.319 0.305 0.327 0.314 0.210 0.216 0.297 0.307
300 0.219 0.198 0.222 0.202 0.276 0.260 0.281 0.266 0.186 0.190 0.251 0.258
400 0.202 0.181 0.205 0.183 0.240 0.222 0.243 0.226 0.168 0.171 0.212 0.216
500 0.191 0.168 0.193 0.170 0.216 0.196 0.216 0.197 0.156 0.158 0.186 0.189
630 0.181 0.157 0.182 0.159 0.197 0.175 0.198 0.177

 

Note:

  • 75°C and 90°C are the conductor temperatures.
  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • These Vc values apply to a balanced three phase circuit in which no current flows in the neutral conductor.

To determine the single phase Vc the current in the neutral conductor needs to be considered by multiplying the three phase value by .

 

 

Table 10

Three Phase Voltage Drop (Vc) at 50 Hz

(Flexible Cord and Flexible Cable)

Conductor size

mm2

Three Phase Voltage Drop (Vc) at 50 Hz, mV/A.m
Single Core Multicore
75°C 90°C
Laid Flat Touching or in a Wiring Enclosure Laid in Trefoil Laid Flat Touching or in a Wiring Enclosure Laid in Trefoil 75°C 90°C
0.5 82.2 82.2 86.1 86.1 82.2 86.1
0.75 54.8 54.8 57.4 57.4 54.8 57.4
1 41.1 41.1 43.1 43.1 41.1 43.1
1.5 28.0 28.0 29.4 29.4 28.0 29.4
2.5 16.8 16.8 17.6 17.6 16.8 17.6
4 10.4 10.4 10.9 10.9 10.4 10.9
6 6.96 6.95 7.29 7.29 6.95 7.29
10 4.03 4.03 4.22 4.22 4.03 4.22
16 2.56 2.56 2.68 2.68 2.55 2.68
25 1.66 1.65 1.74 1.73 1.65 1.73
35 1.18 1.18 1.24 1.24 1.18 1.23
50 0.837 0.831 0.875 0.869 0.827 0.866
70 0.603 0.596 0.630 0.622 0.591 0.618
95 0.473 0.463 0.492 0.483 0.457 0.477
120 0.385 0.373 0.399 0.388 0.367 0.383
150 0.327 0.313 0.338 0.325 0.306 0.318
185 0.287 0.272 0.295 0.280 0.264 0.273
240 0.245 0.227 0.251 0.233 0.219 0.225
300 0.223 0.203 0.227 0.207 0.194 0.198
400 0.202 0.180 0.204 0.183 0.171 0.174
500 0.190 0.167 0.192 0.169 0.158 0.160
630 0.180 0.156 0.181 0.157

 

Note:

  • 75°C and 90°C are the conductor temperatures.
  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • These Vc values apply to a balanced three phase circuit in which no current flows in the neutral conductor.
  • To determine the single phase Vc the current in the neutral conductor needs to be considered by multiplying the three phase value by .

Derating Factor

Table 11

Derating Factors for Groups of Circuits (Single Core – Buried Direct)

 

Cable type: Single Core

Installation Conditions: Buried Direct in Ground

No of Circuits
Derating factor
Touching Distance (S), m
0.15 0.30 0.45 0.60
Trefoil Laid flat
2 0.78 0.81 0.83 0.88 0.91 0.93
3 0.66 0.70 0.73 0.79 0.84 0.87
4 0.61 0.64 0.68 0.74 0.81 0.85
5 0.56 0.60 0.64 0.73 0.79 0.83
6 0.53 0.57 0.61 0.71 0.78 0.82
7 0.50 0.54 0.59 0.69 0.76 0.82
8 0.49 0.53 0.57 0.68 0.76 0.81
9 0.47 0.51 0.56 0.67 0.75 0.81
10 0.46 0.50 0.55 0.67 0.75 0.80
11 0.44 0.49 0.54 0.66 0.74 0.80
12 0.43 0.48 0.53 0.66 0.74 0.80

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

Table 12

Derating Factors for Groups of Circuits (Multicore – Buried Direct)

 

Cable type: Multicore

Installation Conditions: Buried Direct in Ground

No of

Cables in

group

Derating factor
Touching Distance (S), m
0.15 0.30 0.45 0.60
2 0.81 0.87 0.91 0.93 0.95
3 0.70 0.78 0.84 0.88 0.90
4 0.63 0.74 0.81 0.86 0.89
5 0.59 0.70 0.78 0.84 0.87
6 0.55 0.68 0.77 0.83 0.87
7 0.52 0.66 0.75 0.82 0.86
8 0.50 0.64 0.75 0.81 0.86
9 0.48 0.63 0.74 0.81 0.85
10 0.47 0.62 0.73 0.80 0.85
11 0.45 0.61 0.73 0.80 0.85
12 0.44 0.60 0.72 0.80 0.84

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • The derating factors have been determined from the hottest cable in the ground and assume that all cables are of the same thermal grade of insulation.

 

 

Table 13

Derating Factors for Groups of Circuits (Single Core – Enclosed Separately)

 

Cable type: Single Core

Installation Conditions: in underground wiring enclosures – Enclosed Separately

Number of Circuits
Derating factor
Touching Distance (S), m
0.45 0.60
2 0.87 0.91 0.93
3 0.78 0.84 0.87
4 0.74 0.81 0.85
5 0.70 0.79 0.83
6 0.69 0.78 0.82
7 0.67 0.76 0.82
8 0.66 0.76 0.81
9 0.65 0.75 0.81
10 0.64 0.75 0.80
11 0.63 0.74 0.80
12 0.63 0.74 0.80

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 14

Derating Factors for Groups of Circuits (Single core or Multicore – Enclosed)

Cable type: Single Core or Multicore

Installation Conditions: in underground wiring enclosures – multicore cables Enclosed

Separately or more than one single core cables per wiring Enclosures

 Number of Circuits
Derating factor
Touching Distance (S), m
0.30 0.45 0.60
2 0.90 0.93 0.95 0.96
3 0.83 0.88 0.91 0.93
4 0.79 0.85 0.89 0.92
5 0.75 0.83 0.88 0.91
6 0.73 0.82 0.87 0.90
7 0.71 0.81 0.86 0.89
8 0.70 0.80 0.85 0.89
9 0.68 0.79 0.85 0.89
10 0.67 0.79 0.85 0.89
11 0.66 0.78 0.84 0.88
12 0.66 0.78 0.84 0.88

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

Rating Factor

Table 15

Rating Factors (Air and Concrete Slab Temperature)

 

Variance: Air and concrete slab ambient temperature

Installation Conditions: Cable in air or heated concrete slabs

Conductor temperature

°C

Rating factor
Air and concrete slab ambient temperature, °C
15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 100
110 1.16 1.13 1.10 1.07 1.04 1.0 0.96 0.93 0.89 0.85 0.80 0.76 0.71 0.65 0.60 0.53 0.38
90 1.26 1.20 1.15 1.10 1.05 1.0 0.94 0.88 0.81 0.73 0.65 0.57 0.47 0.34 0.19
80 1.31 1.25 1.19 1.12 1.06 1.0 0.92 0.84 0.76 0.66 0.56 0.45 0.27
75 1.35 1.28 1.21 1.14 1.07 1.0 0.91 0.82 0.72 0.60 0.49 0.37

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • For heated concrete slabs, the ambient temperature shall be taken as the operating temperature of the slab.

 

 

Table 16

Rating Factors (Soil ambient Temperature)

 

Variance: Soil ambient temperature

Installation Conditions: Cable buried direct in ground or in underground wiring enclosures

Conductor temperature

°C

Rating factor
Soil ambient temperature, °C
10 15 20 25 30 35 40
110 1.08 1.06 1.03 1 0.97 0.94 0.91
90 1.11 1.07 1.03 1 0.97 0.93 0.89
80 1.13 1.09 1.04 1 0.96 0.91 0.85
75 1.14 1.10 1.05 1 0.95 0.89 0.83

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

Table 17

Rating Factors (Depth of Laying)

 

Cable Types: Single core or multicore

Variance: Depth of laying

Installation Conditions: Cable buried direct in ground and in underground wiring enclosures

Depth of laying

m

Rating factor
buried direct in ground in underground wiring enclosure
Conductor size, mm2 Single Core* Multicore
Up to 50 Above 50 up to 300 Above 300
0.5 1.00 1.00 1.00 1.00 1.00
0.6 0.99 0.98 0.97 0.98 0.99
0.8 0.97 0.96 0.94 0.95 0.97
1.0 0.95 0.94 0.92 0.93 0.96
1.25 0.94 0.92 0.90 0.90 0.95
1.5 0.93 0.91 0.89 0.89 0.94
1.75 0.92 0.89 0.87 0.88 0.94
2.0 0.91 0.88 0.86 0.87 0.93
2.5 0.90 0.87 0.85 0.86 0.93
3.0 or more 0.89 0.86 0.83 0.85 0.92

 

* These rating factors apply to single core cables enclosed separately, or grouped in a single wiring enclosure.

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • The ambient temperature at the surface is to taken at 40°C and not 25°C as at a depth of 0.5m.
  • For depth less than 0.5m, see tables 2(3) and 2(4) of AS/NZS 3008.1.1.

 

 

Table 18

Rating Factors (Thermal resistivity of the soil)

 

Variance: Thermal resistivity of the soil (from 1. 2°C.m/W)

Installation Conditions: Cable buried direct in ground and in underground wiring enclosures

Thermal resistivity of the soil

°C.m/W

Rating factor
Multicore cable buried direct Two or three single core cables buried direct Multicore cable in a wiring enclosure Two single core cables cable in a wiring enclosure* Three single core cables cable in a wiring enclosure*
0.8 1.09 1.16 1.03 1.06 1.08
0.9 1.07 1.11 1.02 1.04 1.06
1.0 1.04 1.07 1.02 1.03 1.04
1.2 1.00 1.00 1.00 1.00 1.00
1.5 0.92 0.90 0.95 0.94 0.92
2.0 0.81 0.80 0.88 0.86 0.83
2.5 0.74 0.72 0.83 0.80 0.77
3.0 0.69 0.66 0.78 0.75 0.71

* These rating factors apply to single core cables enclosed separately, or grouped in a single wiring enclosure.

 

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

American conductor sizes

Table 19

Conversion American conductor sizes (MCM) & (AWG) to mm2

 

MCM Diameter

mm

Area

mm2

MCM Diameter

mm

Area

mm2

1750 33.60 886.7 700 21.25 354.7
1500 31.11 760.1 600 19.67 304.0
1250 28.40 633.4 500 17.96 253.4
1000 25.40 506.7 400 16.06 202.7
900 24.10 456.0 350 15.03 177.3
800 22.71 405.4 300 13.91 152.0
750 22.00 380.0 250 12.70 126.7

 

 

AWG MCM Diameter

mm

Area

mm2

AWG MCM Diameter

mm

Area

mm2

0000 or (4/0) 212 11.684 107 19 1.29 0.912 0.653
000 or (3/0) 168 10.450 85 20 1.02 0.812 0.518
00 or (2/0) 133 9.266 67.4 21 0.810 0.723 0.410
0 or (1/0) 106 8.251 53.5 22 0.642 0.644 0.326
1 83.7 7.348 42.4 23 0.509 0.573 0.258
2 66.4 6.544 33.6 24 0.404 0.511 0.205
3 52.6 5.827 26.7 25 0.320 0.455 0.162
4 41.7 5.189 21.2 26 0.254 0.405 0.129
5 33.1 4.621 16.8 27 0.202 0.361 0.102
6 26.3 4.115 13.3 28 0.160 0.321 0.0810
7 20.8 3.665 10.5 29 0.127 0.286 0.0642
8 16.5 3.264 8.37 30 0.101 0.255 0.0509
9 13.1 2.906 6.63 31 0.0797 0.227 0.0404
10 10.4 2.588 5.26 32 0.0632 0.202 0.0320
11 8.23 2.305 4.17 33 0.0501 0.180 0.0254
12 6.53 2.053 3.31 34 0.0398 0.160 0.0201
13 5.18 1.828 2.62 35 0.0315 0.143 0.0160
14 4.11 1.628 2.08 36 0.0250 0.127 0.0127
15 3.26 1.450 1.65 37 0.0198 0.113 0.0100
16 2.58 1.291 1.31 38 0.0157 0.101 0.00797
17 2.05 1.150 1.04 39 0.0125 0.0897 0.00632
18 1.62 1.024 0.823 40 0.00989 0.0799 0.00501

 

Note:

  • American wire gauge (AWG), also known as the Brown & Sharpe (B & S) wire gauge, is a standardized wire gauge system used since 1857 predominantly in North America for the diameters of electrically conducting wire.
  • In the North American electrical industry, conductors larger than (4/0) or (0000) AWG are generally identified by the area in thousands of circular mils (kcmil), where 1 kcmil = 0.5067 mm2. The next wire size larger than (4/0) or (0000) has a cross section of 250 kcmil. A circular mil is the area of a wire one mil in diameter. One million circular mils is the area of a circle with 1000 mil (1 inch) diameter. An older abbreviation for one thousand circular mils is MCM.

Solid copper & aluminum conductors (Class 1)

Table 20

Solid copper conductors (Class 1) for Single core and multicore cables

 

Nominal Cross sectional area

mm2

Maximum d.c. resistance of conductor at 20°C

O/km

Plain or silver-plated Annealed copper* Tinned annealed copper*
0.5 36.0 36.7
0.75 24.5 24.8
1.0 18.1 18.2
1.5 12.1 12.2
2.5 7.41 7.56
4 4.61 4.70
6 3.08 3.11
10 1.83 1.84
16 1.15 1.16
25 0.727

 

*To obtain the maximum resistance for hard-drawn copper conductors, the tabulated values should be divided by 0.97.

Note:

  • Content from AS/NZS 1125:2001 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

Table 21

Solid Aluminum conductors (Class 1) for Single core and multicore cables

 

Nominal Cross sectional area

mm2

Maximum d.c. resistance of conductor at 20°C

O/km

2.5 12.1
4 7.54
6 5.01
10 3.08
16 1.91
25 1.20
35 0.868
50 0.641
70 0.443
95 0.320
125 0.253
150 0.206
185 0.164
240 0.125
300 0.100
380 0.0800
480 (4×95) 0.0633
600 (4×120) 0.0515
740 (4×185) 0.0410
960 (4×240) 0.0313
1200 (4×300) 0.0250

 

Note:

  • Content from AS/NZS 1125:2001 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

Stranded copper & aluminum conductors (Class 2)

Table 22

Stranded copper conductors (Class 2) for Single core and multicore cables

 

Nominal Cross sectional area

mm2

Minimum number of wires in conductor Maximum d.c. resistance of conductor at 20°C

O/km

Circular or compressed conductor Circular compacted conductor Shaped conductor Plain or silver-plated Annealed copper* Tinned annealed copper*
0.5 3 38.4 39.6
0.75 3 25.3 26.0
1.0 3 21.2 21.6
1.5 3 6 13.6 13.8
2.5 3 6 7.41 7.56
4 7 6 4.61 4.70
6 7 6 3.08 3.11
10 7 6 1.83 1.84
16 7 6 1.15 1.16
25 7 6 6 0.727 0.734
35 7 6 6 0.524 0.529
50 19 6 6 0.387 0.391
70 19 12 12 0.268 0.270
95 19 15 15 0.193 0.195
120 37 18 18 0.153 0.154
150 37 18 18 0.124 0.126
185 37 30 30 0.0991 0.100
240 61 34 34 0.0754 0.0762
300 61 34 34 0.0601 0.0607
400 61 53 53 0.0470 0.0475
500 61 53 53 0.0366+ 0.0369+
630 91 53 53 0.0283+ 0.0286+

 

* To obtain the maximum resistance for hard-drawn copper conductors, the tabulated values should be divided by 0.97.

+ Resistance Values are applicable only to single core cables. For multicore Cables, these resistance values should be multiplied by 1.02.

Note:

  • Content from AS/NZS 1125:2001 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

 

 

 

Table 23

Stranded Aluminum conductors (Class 2) for Single core and multicore cables

 

Nominal Cross sectional area

mm2

Minimum number of wires in conductor Maximum d.c. resistance of conductor at 20°C

O/km

Circular or compressed conductor Circular compacted conductor Shaped conductor
4 7 7.41
6 7 4.61
10 7 3.08
16 7 1.91
25 7 6 6 1.20
35 7 6 6 0.868
50 19 6 6 0.641
70 19 12 12 0.443
95 19 15 15 0.320
120 37 15 15 0.253
150 37 15 15 0.206
185 37 30 30 0.164
240 61 30 30 0.126
300 61 30 30 0.100
400 61 53 53 0.0778
500 61 53 53 0.0605*
630 91 53 53 0.0469*
800 91 53 0.0367
1000 91 53 0.0291

 

* Resistance Values are applicable only to single core cables. For multicore Cables, these resistance values should be multiplied by 1.02.

 

Note:

  • Content from AS/NZS 1125:2001 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

Flexible copper conductors (Class 5)

Table 24

Flexible copper conductors (Class 5) for Single core, multicore cables and flexible cord

 

Nominal Cross sectional area

mm2

Maximum diameter of wires in conductor

mm

Maximum d.c. resistance of conductor at 20°C

O/km

Plain or silver-plated Annealed copper Tinned annealed copper
0.5 0.21 39.0 40.1
0.75 0.21 26.0 26.7
1.0 0.21 19.5 20.0
1.5 0.26 13.3 13.7
2.5 0.26 7.98 8.21
4 0.31 4.95 5.09
6 0.31 3.30 3.39
10 0.41 1.91 1.95
16 0.41 1.21 1.24
25 0.41 0.780 0.795
35 0.41 0.554 0.565
50 0.41 0.386 0.393
70 0.51 0.272 0.277
95 0.51 0.206 0.210
120 0.51 0.161 0.164
150 0.51 0.129 0.132
185 0.51 0.106 0.108
240 0.51 0.0801 0.0817
300 0.51 0.0641 0.0654
400 0.51 0.0486 0.0495
500 0.61 0.0384 0.0391
630 0,61 0.0287 0.0292

 

Note:

  • Content from AS/NZS 1125:2001 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

Minimum copper earthing conductor size

Table 25

Minimum copper earthing conductor size

 

Nominal size of active conductor

mm2

Nominal size of copper earthing conductor

mm2

With copper active conductor With Aluminum, active conductor
1 1*
1.5 1.5*
2.5 2.5
4 2.5
6 2.5
10 4
16 6 4
25 6 6
35 10 6
50 16 10
70 25 10
95 25 16
120 35 25
150 50 25
185 70 35
240 95 50
300 120 70
400 ≥ 120+ ≥ 95+
500 ≥ 120+ ≥ 95+
630 ≥ 120+ ≥ 120+
> 630 ≥ 25% of active size+ ≥ 25% of active size+

 

* These earthing conductors may be used only where incorporated in a multicore cable or flexible cord, other than a lift travelling cable, in accordance with Clause 5.3.3.4(b) & (c) of AS/NZS 3000:2007.

+ A larger earthing conductor may be required to Safety Clause 5.3.3.1.1 of AS/NZS 3000:2007.

 

Note:

  • Content from AS/NZS 3000:2007 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.

Maximum operating temperatures for various types of cable insulations

Table 26

Maximum operating temperatures for various types of cable insulations

 

Type of cable insulation Operating temperatures of conductors, °C
Normal use Maximum permissible Minimum ambient
Thermoplastic V-75 75 75 0
V-90 75 90 0
V-90HT 75 105 0
Cross-linked polyolefin (XLPE) X-90 90 90 *

 

* Refer to manufacturer’s information.

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.
  • Refer to table 1 of AS/NZS 3008.1.1-2017 for other types of insulations.

Temperature limits for insulating material in contact with conductors

Table 27

Temperature limits for insulating material in contact with conductors

 

Material Operating temperatures of conductors, °C
Thermoplastic: V-75, V-90, V-90HT, … up to and including 300 mm2 160
greater than 300 mm2 140
Cross-linked polyolefin (XLPE): X-90, X-90UV, … 250

Note:

  • Content from AS/NZS 3008.1.1-2017 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • Refer to table 53 of AS/NZS 3008.1.1-2017 for other types of materials.

Short circuit current of conductors for 1 second

Table 28

Short circuit current of conductors for 1 second

 

Nominal Conductor Area

mm2

Short circuit current, kA
PVC Insulated Cable XLPE Insulated Cable
75°C 90°C 90°C 90°C
copper Aluminum copper Aluminum copper Aluminum
1 0.111 0.074 0.1 0.066 0.143 0.095
1.5 0.167 0.11 0.15 0.099 0.215 0.142
2.5 0.278 0.184 0.25 0.165 0.358 0.236
4 0.444 0.294 0.4 0.264 0.572 0.378
6 0.666 0.442 0.599 0.396 0.858 0.567
10 1.11 0.736 0.999 0.66 1.43 0.945
16 1.78 1.18 1.6 1.06 2.29 1.51
25 2.78 1.84 2.5 1.65 3.58 2.36
35 3.89 2.58 3.5 2.31 5.01 3.31
50 5.55 3.68 5 3.3 7.15 4.37
70 7.77 5.15 6.99 4.62 10 6.62
95 10.5 6.99 9.49 6.27 13.6 8.98
120 13.3 8,83 12 7.92 17.2 11.3
150 16.7 11.0 15 9.9 21.5 14.2
185 20.5 13.6 18.5 12.2 26.5 17.5
240 26.6 17.7 24 15.8 34.3 22.7
300 33.3 22.1 30 19,8 42.9 28.4
400 39.5 26.1 34.2 22.6 57.2 37.8
500 49.7 32.6 42.8 28.3 71.5 47.3
630 62.2 41.1 53.9 35.7 90.1 59.5

 

Note:

  • 75°C & 90°C are to be considered as conductor temperature at the start of short circuit.
  • 160°C for PVC insulation with conductor up to and including 300mm2, 140°C for PVC insulation with conductor greater than 300mm2 and 250°C for XLPE insulation, are to be considered as conductor temperature at the end of short circuit.
  • The short circuit current for durations up to and including 5 seconds may be calculated with the following formula:

Number of cables installed in conduits

Table 29

Maximum number of single core sheathed cables installed in conduit

 

Cable Size

mm2

Heavy duty rigid UPVC conduit Corflo conduit
20 25 32 40 50 63 80 80 100 100 125 150 100 100 125 150
(NZ) (AUS) (NZ) (AUS) (NZ) (AUS)
PVC/PVC V90
1 5 9 16 26 43 71 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100
1.5 4 7 13 21 36 59 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100
2.5 3 5 10 16 27 44 79 92 > 100 > 100 > 100 > 100 > 100 > 100 > 100 > 100
4 1 3 7 11 19 31 56 64 99 > 100 > 100 > 100 99 > 100 > 100 > 100
6 1 3 6 9 16 26 48 55 85 92 > 100 > 100 85 89 > 100 > 100
10 1 1 4 6 11 18 32 38 58 63 95 > 100 58 60 90 > 100
16 1 1 3 5 8 13 24 28 43 46 70 92 43 45 67 88
XLPE/PVC
25 0 1 1 3 5 9 16 19 29 31 48 62 29 30 45 60
35 0 1 1 2 4 7 13 15 24 26 39 52 24 25 38 50
50 0 1 1 1 3 6 10 12 19 21 31 41 19 20 30 40
70 0 0 1 1 2 4 8 9 15 16 24 31 15 15 23 30
95 0 0 1 1 1 3 6 7 11 12 18 24 11 12 17 23
120 0 0 0 1 1 2 5 6 9 10 15 20 9 10 14 19
150 0 0 0 1 1 2 4 5 7 8 12 16 7 8 12 16
185 0 0 0 0 1 1 3 4 6 6 10 13 6 6 10 13
240 0 0 0 0 1 1 2 3 5 5 8 10 5 5 7 10
300 0 0 0 0 1 1 1 2 4 4 6 8 4 4 6 8
400 0 0 0 0 0 1 1 1 3 3 5 7 3 3 5 6
500 0 0 0 0 0 1 1 1 3 3 4 6 3 3 4 6
630 0 0 0 0 0 0 1 1 1 2 3 4 1 1 3 4

 

Note:

  • Content from AS/NZS 3000:2007 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012.
  • Refer to table C9 of AS/NZS 3000:2007 for other types of conduits (Medium duty corrugated and Medium duty rigid UPVC conduit).

 

 

 

Table 30

Maximum number of two core and earth cables installed in conduit

 

Cable Size

mm2

Heavy duty rigid UPVC conduit Carlo conduit
20 25 32 40 50 63 80 80 100 100 125 150 100 100 125 150
(NZ) (AUS) (NZ) (AUS) (NZ) (AUS)
PVC/PVC V90
1.5 1 1 2 4 7 11 21 24 38 41 62 81 38 40 59 78
2.5 0 1 1 3 5 9 16 19 30 32 48 63 30 31 46 61
4 0 1 1 2 4 7 13 15 23 25 38 50 23 24 36 48
6 0 1 1 2 4 6 12 13 21 23 34 45 21 22 33 43
PVC/PVC V75
10 0 0 1 1 2 4 7 9 13 15 22 29 13 14 21 28
16 0 0 1 1 1 3 6 7 11 11 18 23 11 11 17 22
25 0 0 0 1 1 2 4 5 7 8 12 16 7 8 12 16
PVC/PVC V90

Flat

1 1 2 5 8 14 23 42 48 75 81 > 100 > 100 75 78 > 100 > 100
1.5 1 2 5 8 13 22 40 46 71 77 > 100 > 100 71 74 > 100 > 100
2.5 1 1 3 5 9 15 28 32 50 54 81 > 100 50 52 77 > 100
4 1 1 2 4 6 11 20 23 36 38 58 76 36 37 55 73
6 0 1 1 3 5 9 17 19 30 32 49 64 30 31 47 62
10 0 1 1 2 4 7 12 14 22 24 36 47 22 23 34 45
16 0 0 1 1 2 4 8 9 14 15 23 31 14 15 22 30

 

Note:

  • Content from AS/NZS 3000:2007 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • Refer to table C10 of AS/NZS 3000:2007 for other types of conduits (Medium duty corrugated and Medium duty rigid UPVC conduit).

 

 

 

Table 31

Maximum number of four core and earth cables installed in conduit

 

Cable Size

mm2

Heavy duty rigid UPVC conduit Carlo conduit
20 25 32 40 50 63 80 80 100 100 125 150 100 100 125 150
(NZ) (AUS) (NZ) (AUS) (NZ) (AUS)
PVC/PVC V90
1.5 0 1 1 3 5 9 16 18 29 31 47 61 29 30 45 59
2.5 0 1 1 2 4 6 12 14 21 23 35 46 21 22 33 44
4 0 0 1 1 3 5 6 10 16 18 27 35 16 17 26 34
6 0 0 1 1 2 4 8 9 14 15 23 31 14 15 22 29
PVC/PVC V75
10 0 0 0 1 1 2 5 6 9 10 15 20 9 10 14 19
16 0 0 0 1 1 1 4 4 7 8 12 15 7 7 11 15
25 0 0 0 0 1 1 3 3 5 5 8 11 5 5 8 11
35 0 0 0 0 1 1 2 2 4 4 7 9 4 4 6 9
50 0 0 0 0 0 1 1 1 3 3 5 6 3 3 5 6
70 0 0 0 0 0 1 1 1 2 2 4 5 2 2 3 5
95 0 0 0 0 0 0 1 1 1 1 3 4 1 1 2 3
XLPE/PVC
16 0 0 0 1 1 3 5 6 9 10 15 20 9 10 15 19
25 0 0 0 0 1 1 3 3 6 6 9 12 6 6 9 12
35 0 0 0 0 1 1 2 3 4 5 7 10 4 5 7 9
50 0 0 0 0 0 1 1 2 3 3 6 7 3 3 5 7
70 0 0 0 0 0 1 1 1 2 2 4 5 2 2 4 5
95 0 0 0 0 0 0 1 1 1 1 3 4 1 1 3 4
120 0 0 0 0 0 0 1 1 1 1 2 3 1 1 2 3

 

Note:

  • Content from AS/NZS 3000:2007 has been reproduced with the permission from Standards Australia/New Zealand under Copyright Licence 1708-c012
  • Refer to table C11 of AS/NZS 3000:2007 for other types of conduits (Medium duty corrugated and Medium duty rigid UPVC conduit).